Click here to see  the Procon User Manual.

PL8AI/V - 8 Voltage Input Module

The PL8AI/V is a 8 channel voltage input module. The inputs are isolated from the logic and share a common negative terminal.

The standard setting for the PL8AI/V module is 0 – 10V. An input voltage of 0 – 10Volts represents an output of 0 – 4095 and 2 volts would give a reading of 819 +/- 1LSB.  To obtain an output value of 0 to 4095 for an input signal of 2 to 10V  the offset switch is switched on. An input range of 0(1) to 5Vdc is available by removing the jumper link located on the analogue board inside the enclosure.

PL8AIV

Order Code: PL8AI/V - 8 Voltage Input Module

Analog Inputs

8

Type

Single-Ended

Voltage

0-10Vdc / 0-5Vdc

Offset (switch selectable)

2Vdc (0-10) / 1Vdc (0-5)

Resolution

12 bit (0-4095)

Sample rate

12.5 samples/sec

Input Impedance

25KOhms

Drift

50 ppm/deg.C typ.

Accuracy

0.2 % of span

Isolation (Field & Logic)

1500VAC RMS

Power supply (Field)

+12Vdc to 24Vdc