<< Click to Display Table of Contents >> Eurotherm Chessell 5000 |
![]() ![]() ![]() |
The addressing is the same as that for Modbus TCP/IP.
However, in order to address the other channels, the Modbus TCP/IP address specification
needs to be followed by a semi-colon and an offset.
For "Channel Cfg Data" the offset is multiples of 162.
For example, if the Modbus TCP/IP address was 192.168.1.99,1,2J then:
Channel 1 would be: 192.168.1.99,1,2J
Channel 2 would be: 192.168.1.99,1,2J;162
Channel 3 would be: 192.168.1.99,1,2J;324
Channel 4 would be: 192.168.1.99,1,2J;486
... (up to as many channels as required)
For "Channel RT Data" the offset is multiples of 3.
For example, if the Modbus TCP/IP address was 192.168.1.99,2,2J then:
Channel 1 would be: 192.168.1.99,2,2J
Channel 2 would be: 192.168.1.99,2,2J;3
Channel 3 would be: 192.168.1.99,2,2J;6
Channel 4 would be: 192.168.1.99,2,2J;9
... (up to as many channels as required)
For "Inst Data" there is no offset required as only one is required.